Product Details:

Type Moulded Case
Poles Number 3
Place of Origin Zhejiang, China
Brand Name chko
Model Number 3vu

Detailed Product Description


motor protection circuit breaker(breaker)

3VU series motor protection circuit breakers are applicable for the circuit of 50 50/60Hz, rated insulation voltage 750V, rated opeation current from 0.1 to 63A, they are used for protecting motors from overload, short circuit or phase-failure.2. Main Technical Parameters:

Model

Rated Current

Motor Output

Setting Current Range

Specification

Thermal overload release

Instantaneous over current release

3VU13

0.16

 

0.1-0.16

1.9

-XB00

0.24

0.06

0.16-0.24

2.9

-XC00

0.4

0.09/0.12

0.24-0.4

4.8

-XD00

0.6

0.12/0.18

0.4-0.6

7.2

-XE00

1

0.25

0.6-1

12

-XF00

1.6

0.37/0.55

1-1.6

19

-XG00

2.4

0.75

1.6-2.4

29

-XH00

3.2

1.1

2-3.2

38

-NH00

4

1.1/1.5

2.4-4

48

-XJ00

5

1.5/2.2

3.2-5

60

-NJ00

6

2.2

4-6

72

-XK00

8

3

5-8

96

-NK00

10

 

6-10

120

-XL00

13

4/5.5

8-13

156

-NL00

16

7.5

10-16

190

-XM00

20

7.5

14-20

240

-XN00

20

11

18-25

300

-XP00

3VU16

1.6

0.37/0.55

1-1.6

19

-XG00

2.4

0.75

1.6-2.4

29

-XH00

4

1.1-1.5

2.4-4

48

-XJ00

6

2.2

4-6

72

-XK00

10

3/4

6-10

120

-XL00

16

5.5-7.5

10-16

190

-XM00

25

11

16-25

300

-XN00

32

15

22-32

380

-XP00

40

18.5

28-40

480

-XQ00

52

22

36-52

600

-XR00

63

 

45-63

600

-XS00

motor protection circuit breaker motor protection circuit breaker

Send your message to this supplier
« Prev Product 1 2 3 4 Next Product »

Other Products from this Supplier

Company Info

Changjiang Group Stock Co.,Ltd.
[China]
[Verified Member]

City: Yueqing
Province/State: Zhejiang
Country/Region : China

Business Type:Manufacturer, Agent

View Contact Details

Email this page Bookmark this page Print this Page